TECHNICAL DATA
ALL MODELS
Frontal panel protection: IP65.
Casing: plastic body in resin type
PC+ABS UL94 V-0, inspection window in polycarbonate, buttons in thermoplastic resin.
Dimensions: frontal panel 74x32 mm, depth 60 mm (depth 68 mm only for ID 974 switching).
Installation: on panel, with drilling template 71x29 mm (+0.2/–0.1 mm).
Use temperature: –5…55 °C.
Storage temperature.: –30…85 °C.
Use and storage environment humidity:
10…90 % RH (not condensing).
Viewing range:
• NTC probe: –50…110 °C (-58...230°F)
• PTC probe: –55…140 °C (-67...284°F) without decimal point (selectable through parameter on 3 digit + 1/2 mark display. Analog inputs: two PTC or NTC inputs (programmable by parameter).
Serial: TTL for connection to Copy Card or Televis system.
Digital outputs: 3 relay contacts:
first contact SPDT 8(3)A 250Vac, second contact SPST 8(3)A 250Vac, third contact SPST 5(2) A 250Vac.
Measuring range: from –55 to 140 °C.
Accuracy: 0.5% better than end scale + 1 digit.
Resolution: 1 or 0.1 °C.
Consumption:
• model 230V: 3 VA max.
• model 12V: 1,5 VA max.
Consumption: 3W max.
Power supply: 95...240Vdc ±10%
MODEL 8+8+15A
Digital outputs: 3 relay contacts:
• (A) SPDT 8(3)A (1/2 Hp) 250Vac,
• (B) SPST 8(3)A (1/2 Hp) 250Vac,
• (C) SPST 15A (1 Hp) 250Vac.
Consumption: 1,5 VA max. Power supply: 12 Vac/dc ±10%.
MODEL 8+8+15A + D.I.
Digital input: 1 voltage-free digital input that can be set by parameter.
MODEL with Switching power supply
Digital outputs: 3 relay contacts:
• (A) first contact SPDT 8A 250Vac,
• (B) second contact SPST 3A 250Vac,
• (C) third contact SPST 11A 250Vac.
Warning: check the power supply specified on the instrument label; for relay and power supply capacities, contact the Sales Office).