GENERAL DESCRIPTION
The EWHS 280 humidity sensor is a probe designed to be connected to a humidity measuring device. Output signal is a current signal (4...20 mA).
TECHNICAL DATA
Protection rating: IP54
Mounting: use the clip supplied together with the sensor
Electrical connections: PVC twin wire
Connection cable: 1.5 m (4.9') or 3.0 m (9.8')
Dimensions (mm): 103x25
Power supply: 9…28 Vcc
Power input: 20mA max
Ambient temperature: -10…+60°C (14° to 140°F)
Ambient humidity: 0…100% RH
Humidity sensor: resistive
Humidity measurement range: 15…90% RH
Output current of humidity measurement: 4 (20%)…20mA (100%)
Response time under constant conditions (63%) at 23°C (73.4°F): 60 seconds
Saturation recovery time: 360 seconds
Storage temperature: -20…+70°C (-4 to 158°F)
Number of connection wires: 2 (dark blue: power supply; brown: output)
Maximum load: 250 Ohm
Humidity measurement accuracy (23 °C/73.4°F) :
±5% RH (15..90% RH) (es. 40% RH --> min 35% RH ... max 45% RH)
Air filter: wire mesh
Reverse polarity protection: by diode
Max. air speed: 20m/s