IC 915 Pt100 REAMUR

TECHNICAL DATA
Frontal panel protection: IP65.
Casing: plastic body in resin type
PC+ABS UL94 V-0, inspection window in
polycarbonate, buttons in thermoplastic
resin.
Dimensions: frontal panel 74x32 mm,
depth 59 mm (without wirings).
Installation: on panel, with drilling tem-
plate 71x29 mm (+0.2/–0.1 mm).
Use temperature: –4…44 °R.
Storage temperature.: –24…68 °R.
Use environment humidity: 10…90 % RH
(not condensing).
Storage environment humidity: 10…90% RH
(not condensing).
Viewing range: -160…640°R, with decimal
point, selectable through parameter ndt
on 3 digit & 1 / 2 + mark display.
PLEASE NOTE: viewing is 1/10 °R
Serial: TTL for connection to Copy Card.
Analogue input: one PT100 input.
Digital outputs: 2 SPST outputs on 8(3)A
1/2 hp 250V a , (for relay capabilities see
label on the instrument)
Measuring range: from -160 to 640°R.
Accuracy: 0,5% for all scale + 1 digit; 0,2%
from -120 to 240°R.
Resolution: 0,1°R within 199,9 °R, 1°R over.
Consumption
• model 230V: 3 VA max.
• model 12V: 1,5 VA max.
Power supply: 12 V a / c ±10% or 230V a
±10% 50/60 Hz.


Brochures:      